Our new generation ZW32 type recloser is developed by ourselves. It is a combination of advanced domestic and foreign technology. It embodies our ideas: intelligent, environt-friendly, energy-efficient and maitenance-free. It is a kind of outdoor three phase distribution equipment with 24kv rated voltage, 50/60 Hz frequency. It is mainly used to break, make the load current, overload current and short circuit current in power distribution system. It is used as protecting and controlling equipments in transformer substation, industrial and mining enterprises power distribution system. It is especially suitable for rural power network, places with frequent operation, city and rural power network renewal. ZW32 series outdoor automatic recloser combines the functions of control, protect, measurement, communication, reclosing and recording.
-GB 311.1 the insulation coordination in high voltage power
transmission and distribution equipment
-GB/T 11022 common technical requirement for high
voltage switchgear and controlgear
-DL/T 403 ordering technical requirement for 12-40.5kv
high voltage vacuum circuit breaker
-IEC62271-111 High-voltage switchgear and controlgear–Part 111: Automatic circuit reclosers and fault interrupters for alternating current systems up to 38 kV
-Working temperature:
Max ambient temperature: 65℃
Minimum ambient temperature: -45℃
Max daily temperature difference: 25K
-Humidity:
Daily average should be less than 95%.
Average vapor pressure should be less than 2.2Kpa.
-Altitude: not more than 2000m
-Sunshine intensity: 0.1W/cm2 (wind speed 0.5m/s)
-Max wind speed: 35m/s ( Wind speed means the average value within 10
minutes measured at 10m above ground.)
--Wind pressure: no more than 700Pa
-Load: (10mm ice cover and 17.5m/s wind speed at the same time)
-There is no obvious dust, smoke, corrosive/flammable gases, vapor or salt in the surroundings.
-Seismic intensity: no more than 8 degrees
-External vibration from switchgear and control equipment is negligible.
-External pollution insulation class: Ⅳ
For more details pls contact our engineer.